Product UPS System On Line UPS Liebert Make 10 KVA 1:1 Phase On-Line UPS ( GXT MT+ Series )

Liebert Make 10 KVA 1:1 Phase On-Line UPS ( GXT MT+ Series )

UPS System On Line UPS

116820

Model GXT MT+ 10k

Reset default

Specification

Output Specification
Output Capacity (KVA )
10 Kva
Output Capacity (KW )
8 Kw
Output Power Factor
0.8 Power Factor
Output Phase
1 Phase
Output Voltage
230 Volt
Other Output Voltage
220 Or 240 Volt
Load Crest Factor
3:1
Output Waveform type
Sine Wave
UPS Parallel Upto
Not Available
Efficiency at Full Load
> 90 %
Input Specification
Input Voltage
230 Volt
Other Input Voltage
220 Or 240 Volt
Input Phase
1 Phase
Input frequency
50/60Hz +/- 3 Hz
Input Voltage Range (Output Derated)
110 - 280 Volt
Input voltage range for main operations
165 - 185 Volt
Input Power Factor
>0.99 None
Batteries & Runtime
Battery DC Bus
192 - 240 VDC
Maximum Charger Capacity
6 Amp.
Battery Position Option
External
Battery Type Compatibility
SMF Battery
Approved Battery Capacity (AH)
17 - 200 Amp.
Communication & Management
Control panel
LCD Display
SNMP Management
Optional
Audible noise at 1 meter from surface of unit
58 < Decibal
Physical
Maximum Height
318 Mm
Maximum Width
190 Mm
Maximum Depth
442 Mm
Net Weight
23 Kg
Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
5 - 95 % Rh
Other Specifications
Technology
Double Conversion Online

Features

Liebert GXT-MT+ 6-10 kVA Feature
General Features
IGBT Based Rectifier
True Online Double Conversion with DSP Control Technology for High Performance and Reliability
New Graphical LCD Display Provides UPS Data, Alarms and Helps in faults diagnostics and trouble shooting
Double Conversion Efficiency upto 92%
Active Input Power Factor Correction 0.99
0.8 Output Power Factor
Wide Input Voltage window (110 - 280 Vac) for Indian Environmental Condition and for Optimized Battery Performance
Configurable Output Voltage (200/208/220/230/240 Vac.)
Generator Compatible with Wide Input Frequency Range (40 Hz-70 Hz)
4 Stage Extendable Charging Design for optimized Battery Performance
Adjustable Battery Charging Current 1/2/4/6 Amps according to Battery Capacity and Rating
50/60 Hz automatic frequency converter mode
Intelligent Monitoring with Standard RS232/USB Port Plus Slot Available for RS485/Dry Contact/SNMP Card
Inbuilt OVCD

Documentation

Item Catalogue
GXT MT+ 10k ( Download )
pdf

Options