Output Specification
Output Capacity (KVA )
120 KVA
Output Capacity (KW )
120 KW
Output Power Factor
1 Power Factor
Output Phase
3 Phase
Output Voltage
380 Volt
Other Output Voltage
400 Or 415 Volt
Efficiency at Full Load
> 96 %
Output Voltage Distortion
< 2 %
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
UPS Parallel Upto
4 Nos.
Input Specification
Input Voltage
380 Volt
Other Input Voltage
400 Or 415 Volt
Input Phase
3 Phase
Input frequency Range
40 - 70 Hz
Input Voltage Range (Output Derated)
228 - 475 Volt
Input voltage range for main operations
340 - 475 Volt
Input Power Factor
0.99
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input Voltage THD
< 3 %
Batteries & Runtime
Battery Position Option
External
Approved Battery Capacity (AH)
100 - 200 Amp.
Battery Circuit Breaker
Inclusive
Battery DC Bus
384 - 480 VDC
Battery Type Compatibility
SMF/ Li-Ion battery
Maximum Charger Capacity
30 Amp.
Communication & Management
Control panel
LCD Display
SNMP Management
Optional
Physical
Maximum Height
2000 Mm
Maximum Width
600 Mm
Maximum Depth
1000 Mm
Net Weight
430 Kg
Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Protection Class
IP20
Other Specifications
Technology
Double Conversion Online

Features

Liebert® eXM 80-200 KVA Features & Benefits
General Features
Efficient power protection that can meet your capital requirements. Our latest ECO Mode option delivers over 99% efficiency,while the Double Conversion Mode has been optimized to exceed 96%.
Flexible configurations provides an ideal mix of both row-based and room-based benefits, optimized to deliver excellent performance at low total cost of ownership and allow organizations to meet stringent Service Level Agreements
Reliability is the epicenter of Liebert eXM. Its Internal and external architecture is rugged enough to handle input faults, load faults, temporary overloads, input power disturbances and even industrial environment
Double Efficiency exceeding 96% at partial load
ECO mode availability for parallel configurations
Unity output PF ( kVA=kW)
Powerful battery charging capability
Flexible air flow management; from back and top
Top or bottom cable entry
Integrated transformer option
Full frontal access for installation and service
LIFE™ remote diagnostic and preventive monitoring service
Robust internal architecture makes it suitable for light industrial application¿