Product UPS System Industrial UPS Vertiv Liebert Make 100 KVA Industrial On-Line UPS with Isolation Transformer

Vertiv Liebert Make 100 KVA Industrial On-Line UPS with Isolation Transformer

UPS System Industrial UPS

955800

Model Hipulse U 100 KVA

Reset default

Specification

Output Specification
Output Capacity (KVA )
100 KVA
Output Capacity (KW )
90 KW
Output Power Factor
0.9 Power Factor
Output Phase
3 Phase
Output Voltage
430 Volt
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
> 94 %
Output Voltage Distortion
< 3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
+/- 0.1% for 50/60Hz Nominal
Load Crest Factor
3:1
Output Voltage THD
< 3% linear load and <5% non-linear load
Transfer Time
< 0 ms
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Static Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
Input Specification
Input Voltage
415 Volt
Other Input Voltage
384 Or 415 Volt
Input Phase
3 Phase
Input frequency
50 Or 60 Hz
Input Power Factor
0.99
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input Protection
Fuse
Input Voltage THD
< 3 %
Batteries & Runtime
Battery DC Bus
408 - VDC
Battery Type Compatibility
SMF Battery
Battery Position Option
External
Battery Circuit Breaker
Optional
Approved Battery Capacity (AH)
100 - 200 Amp.
Maximum Charger Capacity
55 Amp.
Communication & Management
Control panel
LCD Display
SNMP Management
Optional
Power Management Software
Not Available
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
< 42 Decibal
Physical
Maximum Height
1100 Mm
Maximum Width
900 Mm
Maximum Depth
800 Mm
Net Weight
900 Kg
Colour
Black
Environmental
Operating Temperature
0. - 55 °C
Operating Relative Humidity
0 - 95 %
Operating Elevation
0 1000
Storage Temperature
0 - 65 °C
Storage Relative Humidity
0 - 95 %
Storage Elevation
0 - 1000 Meters
Protection Class
IP20
Compliances
Compliance
EN/IEC 62040-1, IEC 62040-2, IEC 62040-3, IEC 62040-4
Approvals
CE, EAC, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, IEC 62040-4, ISTA 2B, RCM, WEEE
Other Environmental Compliance
Compliant
Other Specifications
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Surge Protection
Yes

Documentation

Item Catalogue
Hipulse U 100 KVA ( Download )
pdf

Options