The Liebert S600E offers best-in-class efficiency of up to 91% over a wide range of load conditions, resulting in significant OPEX cost savings. S600E's integrated Smart Sleep technology in ECO mode provides a superlative efficiency of up to 94%. Available in different wattage versions, Liebert S600E is ideal in edge of networks, light industrial applications and data centers, blending easily into any virtualized environment and providing comprehensive power protection at lower operating costs.

Benefits

High Availability

Inbuilt isolation transformer. Protects UPS and load from high voltage fluctuations.
Early Warning of UPS System Status. Multiple audible and visual alarms immediately alert you to critical issues.
Periodic Battery Testing. Provides automatic and manual self-diagnostic battery testing for peace of mind.
Power-Factor Correction. Prevents noise, harmonics, and distortion from being passed on to connected loads or from being fed back to the utility.
Lightning and Surge Protection. The transient voltage surge suppresion circuitry inside the Liebert S600E provides additional protection for the connected equipment.
Wide Input Voltage Window. Prolongs battery life by allowing the UPS to maximize the use of utility power before transferring to the battery when the input voltage exceeds specified limits.

Features

Inbuilt isolation transformer
Unity power factor
Efficiency >91% with inbuilt transformer
Higher operating temperature: 0 to 50
Settable battery options
Operates in a parallel configuration up to 4 nos
LI-on battery compatible
Graphical screen system LCD display provides user-friendly operating interface
Integrated SNMP for monitoring
Model Super600E 10K33

Reset default

Specification

Output Specification
Output Capacity (KVA )
10 KVA
Output Capacity (KW )
10 KW
Output Power Factor
1 Power Factor
Output Phase
3 Phase
Output Voltage
400 Volt
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
> 91 %
Output Voltage Distortion
<1 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Load Crest Factor
3:1
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
UPS Parallel Upto
4 Nos.
Input Specification
Input Voltage
380 Volt
Other Input Voltage
400 Or 415 Volt
Input Phase
3 Phase
Input frequency
50 Or 60 Hz
Input frequency Range
40 - 70 Hz
Input Voltage Range (Output Derated)
288 - 498 Volt
Input voltage range for main operations
305 - 498 Volt
Input Power Factor
0.99
Input Connections
Hard Wire 5-wire (3PH + N + G)
Batteries & Runtime
Battery DC Bus
384 - 480 VDC
Battery Type Compatibility
SMF/ Li-Ion battery
Battery Circuit Breaker
Approved Battery Capacity (AH)
17 - 200 Amp.
Maximum Charger Capacity
13 Amp.
Communication & Management
Control panel
LCD Display
SNMP Management
Optional
Power Management Software
Optional
Interface Port(s)
LCD Display
Audible noise at 1 meter from surface of unit
<65 Decibal
Physical
Maximum Height
1300 Mm
Maximum Width
335 Mm
Maximum Depth
654 Mm
Net Weight
175 Kg
Environmental
Operating Temperature
0 - 50 °C
Operating Relative Humidity
5 - 95 %
Protection Class
IP20
Other Specifications
Technology
Double Conversion Online

Documentation

Item Catalogue